The maximum capacitance load for the RPD-65C is 470uF. Exceeding this value may cause instability or oscillation.
While the RPD-65C can operate up to 80°C, its reliability and lifespan may be affected above 60°C. Derating the output power or using a heat sink is recommended for high-temperature applications.
The RPD-65C meets various safety certifications, including UL, CE, and EAC. However, the final product must also meet these certifications. Ensure that your product design and testing comply with the relevant safety standards.
Mean Well recommends a minimum clearance of 5mm around the RPD-65C for heat dissipation and electrical isolation. A well-designed PCB layout with proper thermal management is crucial for reliable operation.
Yes, the RPD-65C can be used in redundant or parallel configurations, but it's essential to follow Mean Well's guidelines and recommendations for proper implementation to ensure reliable operation and avoid potential issues.