The maximum cable length for the analog inputs is 100 feet (30.5 meters) for a single-ended connection and 200 feet (61 meters) for a differential connection.
Yes, the MP120D4 can be powered by a 24V DC power supply, but it's recommended to use a regulated power supply to ensure stable operation.
The analog output ranges can be configured using the Opto 22 software, such as OptoOPC or PacDisplay. The software allows you to set the output range, scaling, and offset for each analog output channel.
The response time for the analog inputs is typically 10-20 milliseconds, depending on the input range and filter settings.
Yes, the MP120D4 can be used with third-party PLCs or HMIs that support Modbus RTU or TCP communication protocols.